I NSTALLATION M ANUAL September 2009 Document #: LT-2010 Rev.2 WARNING : This manual contains information on limitations regarding product use and

Página 2

4Addressable Input CircuitsThere are two classes of addressable input circuits supported by the Control Unit:• "Class A" (Style 6) - This is

Página 3 - Table of Contents

MR-2900 Installation Manual51.6 Terminal BoardField connections are terminated on the MR-2936 Terminal Board, which in addition to terminal blockscont

Página 4

61.8 Power SupplyThe Power Supply (MR-2905) is rated at 8A unregulated, providing the system with primary DC power. It iscomplete with a battery charg

Página 5 - List of Figures and Tables

MR-2900 Installation Manual7For NFAPA Style 7 connection of the network, port 1 of node 1 is connected to port 2 of node 2. Port 1 ofnode 2 is connect

Página 6

82.0 Installation2.1 Unpacking the MR-2900The basic MR-2900 package includes the following components:BackboxOuter door including:•Lock• Display windo

Página 7 - 1.0 Technical Information

MR-2900 Installation Manual92.2 Mounting and Assembling the MR-2900Surface and Flush MountingThe MR-2900 can be mounted in either flush or surface mou

Página 8

102.3 Internal Assembly• Attach AC wiring to the AC Terminal Block. Attach green ground wire to ground screw onbackplate.• Place the batteries in the

Página 9 - 1.4 Input Circuits

MR-2900 Installation Manual11Figure 4: Back Box Dimension and Knockout Reference29-1/2"(750 mm)14-1/2" (368 mm)27-1/2"(699 mm)1-1/4&quo

Página 10 - Isolation

122.4 WiringPower ConnectionsThe Main Control Unit requires an AC power supply. See Figures 5 and 6 below.The batteries forming the Battery Pack are w

Página 11 - 1.7 Annunciator Strip

MR-2900 Installation Manual13Conventional Style D (Class A) CircuitThis is a 4-wire power-limited and supervised StyleD (Class A) initiating device ci

Página 13 - MR-2900 Installation Manual

14Normally Closed CircuitThis is a 2-wire non-supervisory circuit and issupported by the MR-2928 module. This circuit islisted by UL for connection to

Página 14 - 2.0 Installation

MR-2900 Installation Manual15Addressable Style 6 (Class A) CircuitThis is a 4-wire power-limited and supervised Style 6 (ClassA) communications circui

Página 15

16Addressable ModulesThe addressable module extended circuits are wired as shown on the next page in Figures 15 - 20.Figure 15: MRI-M500M WiringFigure

Página 16 - 2.3 Internal Assembly

MR-2900 Installation Manual17Figure 17: MRI-M502M WiringFigure 18: MRI-M500S Wiring for Signalling Circuits

Página 17 - BB-2920B

18Style Y (Class B) Bell CircuitThis is a 2-wire Style Y (Class B) power-limited andsupervised signalling (notification appliance) circuit.Devices and

Página 18 - 2.4 Wiring

MR-2900 Installation Manual19Style Z (Class A) Bell CircuitThis is a 4-wire Style Z (Class A) power-limited andsupervised signalling (notification app

Página 19 - TWO CIRCUITS

20Inner Door Ribbon CablesTwo ribbon cables connect the Terminal Board to the MainCircuit Board. These cables are on the hinged side of theInner Door

Página 20

MR-2900 Installation Manual21Table 5: Maximum Capacitance for Network Baud RatesRS-232 Network WiringRS-232 Network wiring uses three (3) wires betwee

Página 21

22Annunciator, UDACT and Reverse Polarity WiringThe MR-2614 and MR-2644 Annunciators, the MR-2900-CITY Reverse Polarity module and the MR-2900-DACT Di

Página 22 - Figure 16: MRI-M501 Wiring

MR-2900 Installation Manual233.0 Technical SpecificationsElectrical RatingsAC Line Voltage 120 V, 60 Hz / 240 V, 50 Hz2A / 1AAC Brownout@120V 90 VAC N

Página 23 - Figure 17: MRI-M502M Wiring

MR-2900 Installation ManualiTable of Contents1.0 Technical Information ...

Página 24 - Regulated 24 FWR

24Bell (Notification Appliance) CircuitsNumber & Type 8 Class B, NFPA Style Y/ Class A, NFPA Style ZSupervisory Current 1.0 mA, power limitedAlarm

Página 25 - Converter

MR-2900 Installation Manual254.0 Parts ListModel DescriptionBasic Control UnitMR-2900 Basic Control Unit (with or without MR-2920 strip printer)Option

Página 26

265.0 Appendix A: Power Supply and Battery CalculationsÒ See 6.0 Appendix B: ULC Listed Compatible Smoke Detectors on page 28 and 7.0 Appendix C: UL L

Página 27

MR-2900 Installation Manual275.1 GeneralBatteries are designed and manufactured for a specific use. "Standby" is one of these uses. They are

Página 28 - Ω resistor across the MR

286.0 Appendix B: ULC Listed Compatible Smoke DetectorsThe following conventional smoke detectors are ULC listed for compatibility with the MR-2900Con

Página 29 - 3.0 Technical Specifications

MR-2900 Installation Manual29Simplex Fenwal2098-9110 PSD-7131/70-201000-001 42EdwardsPSD-7131/70-201000-002 426249C 100 PSD-7131/70-201000-003 426250C

Página 30 - Ω Resistor, EOL-103

306.1 ULC Listed Compatible Addressable DevicesModel DescriptionTypical CurrentDraw µAMRI-1251 Ionization type smoke detector 300MRI-1251B Ionization

Página 31 - 4.0 Parts List

MR-2900 Installation Manual317.0 Appendix C: UL Listed Compatible Devices7.1 UL Listed “Class B” Smoke DetectorsThe following Listed 2-wire smoke dete

Página 32

32Fenwal CPD-7023 I3FE1 CPD-001 FE01A 80 μACPD-7023 I3FE1 CPD-002 FE02A 80 μACPD-7023 I3FE1 CPD-003 FE03A 80 μACPD-7023 I3FE1 CPD-005 FE05A 80 μACPD-7

Página 33 - 5.1 General

MR-2900 Installation Manual33Gentex 224 -1 N/A N/A224-25 -1 N/A N/AHochiki SIF-24F HD-2 HS-221D HB-4 102 μASIF-24F HD-2 YBA-M221 HB-4 102 μASIH-24F HD

Página 35

347.2 UL Listed “Class A” Smoke Detectors The following Listed 2-wire smoke detectors and bases are compatible with the MR-2900 Control Panelusing the

Página 36

MR-2900 Installation Manual357.3 UL Listed Notification AppliancesThe following notification appliances, where a current rating is shown, may be used

Página 37

36CH-CF1-WS-24-CF-W Strobe Chime 20 25CH-DF1-WS-24-VF-R Strobe Chime 20 25CH-DF1-WM-24-VF-R Strobe Chime 20 8846T-G6-24-WS-24-HF-R Strobe Bell, 6 in.

Página 38

MR-2900 Installation Manual37AMT-24-LSM Multitone Strobe Signal, non sync 48 115AMT-24-MS Multitone Strobe Signal, non sync 48 135AMT-24-IS Multitone

Página 39

38RSS-2415C Strobe - 70RSS-243OC Strobe - 107RSS-2475C Strobe - 215RSS-24100C Strobe - 250RSSP-2415C Strobe, retrofit plate - 70RSSP-2430C Strobe, ret

Página 40

MR-2900 Installation Manual39GX90S-4-60 Piezo Horn/Strobe 60 cd 130 (combined)GX90S-4-110 Piezo Horn/Strobe 110 cd 235 (combined)GXS-4-15 Strobe 15 Cd

Página 41

40P241575 (R) (W) Horn/Strobe 39 64P2475 (R) (W) Horn/Strobe 39 159P24110 (R) (W) Horn/Strobe 39 191P241575K Horn/Strobe 39 64P2475K Horn/Strobe 39 15

Página 42

MR-2900 Installation Manual41SS241575ADAS Strobe - 180MASS2415ADAS Horn/Strobe 59 125MASS241575ADAS Horn/Strobe 59 180RP2415ADA Strobe - 90RP241575ADA

Página 43

427.5 UL Listed Analog Addressable DevicesThe following Listed analog addressable smoke detectors, detector bases, monitor modules, controlmodules and

Página 44

MR-2900 Installation Manual437.6 UL LIsted Compatible Door Holder/ReleasersThe following listed door holders are compatible with the MR-2900 and MR-24

Página 45

MR-2900 Installation ManualiiiList of Figures and TablesFigure 1: Basic Network Communication Flow ...

Página 46

448.0 Appendix D: Interconnection to Other Equipment8.1 Radionics 2071C and 2071ACThe wiring between the MR-2900 and the Radionics 2071C and 2071AC Di

Página 47

MR-2900 Installation Manual458.2 Silent Knight 5104The wiring between the MR-2900 and the Silent Knight 5104 Dialer is as shown in the following diagr

Página 48

468.3 CTM City Tie ModuleThe CTM is designed to interface between a control panel and a local city tie box. The interface from thecontrol panel is via

Página 49

MR-2900 Installation Manual478.4 Keltron 3158 TTMThe Keltron 3158 TTM and the MR-2900 are wired together as shown below:Addressable control modules ca

Página 50 - MRI-500C

9.0 Warranty & Warning Information489.0 Warranty & Warning Information9.1 Warning Please Read Carefully Note to End Users: This equipment is s

Página 51

MR-2900 Installation Manual49breakdowns, interruptions, loss, destruction, alteration or other problems in the use of a product arising our of, or cau

Página 52 - 8.3 CTM City Tie Module

9.0 Warranty & Warning Information509.2 Limited Warranty Secutron Inc. warrants the original purchaser that for a period of two years from the dat

Página 53 - 8.4 Keltron 3158 TTM

MR-2900 Installation Manual519.5 Out of Warranty Repairs Secutron Inc. will at its option repair or replace out-of-warranty products which are returne

Página 57 - 9.5 Out of Warranty Repairs

© 2009 Secutron, Inc. Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) SECUTRON (888) 732-8876 Fax: (905) 660-4113 U.S.A4575 Witmer Indus

Página 58

MR-2900 Installation Manual11.0 Technical Information1.1 GeneralThe MR-2900 Fire Alarm Control Unit provides capability for up to 24 Input Circuits, 8

Página 59

2Communication PortsThe Control Unit has 6 communication ports available:• Port #1- network (Proprietary)• Port #2- network (Proprietary)• Port #3- ge

Página 60 - © 2009 Secutron, Inc

MR-2900 Installation Manual31.3 Front PanelThe system controls consist of 12 system switches and a 20position alphanumeric keypad. The 12 system switc